OUTPUT Output Capacity Details 12.6kVA (208V) total capacity 20A max per breakered outlet bank 16A max per C19 outlet 12A max per C13 outlet Frequency Compatibility 50 / 60 Hz Output Receptacles (21) C13 (3) C19 Output Nominal Voltage 208 Overload Protection 3 20A circuit breakers, 1 per outlet bank Customized Load Management Receptacles Each outlet is individually controllable via remote interface
INPUT PDU Input Voltage 208 Recommended Electrical Service 50A 208V with Hubbell CS8365C outlet Maximum Input Amps 35 PDU Plug Type HUBBELL CS8365C 50A Input Cord Length (m) 3.05 Input Phase 3-Phase
PHYSICAL Material of Construction Metal Form Factors Supported Vertical rackmount installation supported with included mounting brackets supports tooless mounting in button-mount compatible racks PDU Form Factor 0U Vertical
ENVIRONMENTAL Storage Temperature Range 5o to 122oF (-15o to 50oC) Relative Humidity 5 to 95% non-condensing Operating Elevation (ft.) 0-10,000 Operating Elevation (msnm) 0-3000
COMMUNICATIONS SNMP Compatibility Yes, pre-installed SNMPWEBCARD provides remote monitoring via web, telnet, SSH and SNMP management systems
CERTIFICATIONS TAA Compliant Option TAA Compliant Version Available - Order Tripp Lite PDU3VSR10H50TAA Certifications Tested to UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS compliant